Using the top-shelf technology and top quality materials (of european origin) in our production process, RADIASTAR is producing finwall panels with following characteristics:
| Panel height: | B = 400-1.600 mm |
| Fin strip thickness: | S = 1.0, 1.2 or 1,5 mm |
| Fin depth: | H = 40(35) – 400 mm |
| Fin distance: | P = 45 mm (standard, min. 38mm) |
Corrugated wall tank has to endure high mechanical loads which can occur during operation or transport of the distribution transformer. Our experience, acquired over decades of successful manufacturing development, combined with modern technology and high-quality welding, results in final products which fulfill the highest quality standards.
Corrugated walls are made of cold-rolled steel in coils. In a hermetically sealed transformer, while in operation, there is always some volume change of the transformer liquid, caused by temperature change and it has to be compensated by finwalls (hermetically sealed tanks) or by tank conservator mounted on top (in case of non-hermetic transformer tanks). The most complex component is the cover, because it not only seals the tank (by bolting or welding it to the tank), but it hosts most of the transformer equipment connections.
The transformer adopts a fully oil-filled sealed structure, and the transformer changes its oil body due to changes in temperature and load, which is completely adjusted by the flexibility of the transformer tank. It has strong lightning resistance and short-circuit resistance. The energy-saving effect is more obvious, and the outer size of the transformer is reduced.
GB/T 1094.1~2-1996 Power Transformer
GB/T 1094.3.5-2003 Power Transformer
GB/T6451-2008 Technical Parameters and Requirements for Three-phase Oil-immersed Power Transformers IEC60076
High ambient temperature: +40℃
Low ambient temperature: -25℃
Altitude: <1000m. We can also customize according to your demand.
Monthly average relative humidity: 90% (20℃)
Installation location: Chemical plants, factories, remote places and other harsh environments.
| Rated capacity (KVA) | Voltage | Connection group tab | Loss | No-load current (%) | Resistant voltage | Weight | Measure(MM) | ||||||
| High-voltage (kv) | Extend connection | Low-voltage (kv) | No-load | Load | Empty weight | Oil weight | Total weight | Length* Width | Height (H) | ||||
| 20 | 6 6.3 10 10.5 113335 | ±5% (±2×2.5%) | 0.4 | Yyn0 or Dyn11 | 105 | 480 | 3 | 4 | 135 | 75 | 280 | 1075*695 | 910 |
| 30 | 130 | 600 | 2.1 | 175 | 85 | 335 | 1105*700 | 950 | |||||
| 50 | 170 | 870 | 2 | 215 | 75 | 360 | 775*775 | 945 | |||||
| 63 | 200 | 1040 | 1.9 | 275 | 105 | 470 | 1170* | 1065 | |||||
| 80 | 250 | 1250 | 1.8 | 280 | 90 | 455 | 820*820 | 980 | |||||
| 100 | 290 | 1500 | 1.6 | 315 | 95 | 500 | 820*820 | 1005 | |||||
| 125 | 340 | 1800 | 1.5 | 365 | 105 | 580 | 850*850 | 1045 | |||||
| 160 | 400 | 2200 | 1.4 | 425 | 110 | 660 | 1135*1135 | 1075 | |||||
| 200 | 480 | 2600 | 1.3 | 500 | 130 | 775 | 1190*1190 | 1120 | |||||
| 250 | 560 | 3050 | 1.2 | 595 | 150 | 915 | 1215*1215 | 1140 | |||||
| 315 | 670 | 3650 | 1.1 | 700 | 170 | 1075 | 1285*1285 | 1200 | |||||
| 400 | 800 | 4300 | 1 | 865 | 195 | 1280 | 1305*1305 | 1285 | |||||
| 500 | 960 | 5150 | 1 | 985 | 220 | 1490 | 1455*1455 | 1275 | |||||
| 630 | 1200 | 6200 | 0.9 | 4.5 | 1140 | 250 | 1735 | 1555*1555 | 1285 | ||||
| 800 | 1400 | 7500 | 0.8 | 1400 | 290 | 2110 | 1660*1660 | 1375 | |||||
| 1000 | 1700 | 10300 | 0.7 | 1560 | 400 | 2475 | 1685*1685 | 1550 | |||||
| 1250 | 1950 | 12000 | 0.6 | 1915 | 465 | 2985 | 1805*1805 | 1505 | |||||
| 1600 | 2400 | 14500 | 0.6 | 2330 | 530 | 3745 | 1840*1840 | 1690 | |||||